diff --git a/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml b/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml index 3b40bde23..d01cd1f67 100644 --- a/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml @@ -1617,7 +1617,11 @@ MMCWDPC: guid: "71874ee4-5596-4e90-ad14-8716a6b6de3a" description: "Minimum water differential pressure control for mechanical cooling in a hydronic system." is_abstract: true + opt_uses: + - bypass_valve_percentage_sensor + - failed_bypass_valve_alarm uses: + - bypass_valve_percentage_command - low_limit_mechanical_cooling_differential_pressure_sensor - low_limit_mechanical_cooling_differential_pressure_setpoint implements: @@ -1645,6 +1649,8 @@ WDPC2X: opt_uses: - pressurization_request_count - run_command + - high_differential_pressure_alarm + - low_differential_pressure_alarm uses: - differential_pressure_sensor_1 - differential_pressure_sensor_2 @@ -2457,6 +2463,7 @@ CHWRC: opt_uses: - chilled_water_flowrate_sensor - chilled_water_valve_percentage_sensor + - cooling_request_count - cooling_thermal_power_capacity - discharge_air_temperature_sensor - leaving_cooling_coil_temperature_sensor @@ -4434,7 +4441,6 @@ HXRWISOVPM: implements: - MONITORING - HXSWISOVM: guid: "3a617a80-2ab5-4eb5-9cf5-c327359a03c6" description: "Heat exchanger supply isolation water valve control." @@ -4445,7 +4451,6 @@ HXSWISOVM: implements: - MONITORING - HXRWISOVM: guid: "48cee686-e728-4996-be87-0a280ecf9733" description: "Heat exchanger return isolation water valve control." @@ -4456,6 +4461,18 @@ HXRWISOVM: implements: - MONITORING +HXCRWISOVPM: + guid: "7fd2b89b-013d-4bad-833c-2b307a63cda5" + description: "Heat exchanger condensing return water isolation valve percentage control." + is_abstract: true + opt_uses: + - failed_heat_exchange_condensing_return_water_isolation_valve_alarm + uses: + - heat_exchange_condensing_return_water_isolation_valve_percentage_command + - heat_exchange_condensing_return_water_isolation_valve_percentage_sensor + implements: + - MONITORING + PWECVC: guid: "c7d64d95-0215-4c9a-b422-a4fb7004f3e3" description: "Process water electricconductivity drain valve control." @@ -4476,6 +4493,30 @@ PWISOVM: implements: - MONITORING +PSWISOVPM: + guid: "e30d558a-61c5-4b9f-8511-9fc460117f7a" + description: "Process supply water iso valve control." + is_abstract: true + opt_uses: + - failed_process_supply_water_isolation_valve_alarm + uses: + - process_supply_water_isolation_valve_percentage_command + - process_supply_water_isolation_valve_percentage_sensor + implements: + - MONITORING + +PRWISOVPM: + guid: "c87142d1-ffef-45ea-ab22-6e81b8393de4" + description: "Process return water iso valve control." + is_abstract: true + opt_uses: + - failed_process_return_water_isolation_valve_alarm + uses: + - process_return_water_isolation_valve_percentage_command + - process_return_water_isolation_valve_percentage_sensor + implements: + - MONITORING + PWVPM: guid: "2335c3b8-b27f-4ef0-b15b-7df5e8d25e4a" description: "Process water valve percentage control." @@ -7526,6 +7567,7 @@ DAIDC: - MONITORING opt_uses: - failed_discharge_air_isolation_damper_alarm + - discharge_air_isolation_damper_percentage_sensor RAIDC4X: diff --git a/ontology/yaml/resources/HVAC/entity_types/CDWS.yaml b/ontology/yaml/resources/HVAC/entity_types/CDWS.yaml index aad2af504..f15d392e3 100644 --- a/ontology/yaml/resources/HVAC/entity_types/CDWS.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/CDWS.yaml @@ -245,7 +245,7 @@ CDWS_SWTC_WSEBYPVPM: CDWS_SWTC_WDPC_CLPM_WFRM_MWFRM: guid: "35a284ef-332d-4e2f-b3f2-4eb94ce3d274" - description: "Chilled water system with supply temperature control, differential pressure control, and thermal load, flowrate and makeup water flowrate monitoring." + description: "Condensing water system with supply temperature control, differential pressure control, and thermal load, flowrate and makeup water flowrate monitoring." is_canonical: true implements: - CDWS @@ -255,6 +255,17 @@ CDWS_SWTC_WDPC_CLPM_WFRM_MWFRM: - WFRM - MWFRM +CDWS_SWTC_WFRM_MWFRM_BWFRM: + guid: "30b52a03-a020-4d65-8c57-bb9cb43e8b15" + description: "Condensing water system with flowrate control, blowdown and makeup water flowrate control." + is_canonical: true + implements: + - CDWS + - SWTC + - WFRM + - MWFRM + - BWFRM + ################################### ### Existing Non-standard Types ### ################################### diff --git a/ontology/yaml/resources/HVAC/entity_types/CH.yaml b/ontology/yaml/resources/HVAC/entity_types/CH.yaml index 9e3807970..1414b4b4f 100644 --- a/ontology/yaml/resources/HVAC/entity_types/CH.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/CH.yaml @@ -1031,6 +1031,57 @@ CH_SS_SWTC_DX2SWC_WDPM_RWISOVM_REFSM_REFPM: - REFSM - REFPM +CH_SS_SCHWTC_CHWDPC_CHWSWISOVPM_CWDT_CWDPM_CWRISOVPM_HXCRWISOVPM_CLPM: + guid: "c51bcdbe-1899-4e9e-9722-0b786b4dcdaf" + description: "Water cooled chiller with isolation on chilled and condensing water side, condensing water heat exchange isolation and cooling thermal power monitoring." + is_canonical: true + implements: + - CH + - SS + - SCHWTC + - CHWDPC + - CHWSWISOVPM + - CWDT + - CWDPM + - CWRISOVPM + - HXCRWISOVPM + - CLPM + +CH_SS_SCHWTC_CHWDPC_CWDT_CWDPM_CHWSWISOVPM_CHWRWISOVPM_PSWISOVPM_PRWISOVPM_CWRISOVPM_HXCRWISOVPM_CLPM: + guid: "75203ebf-976f-4fef-84a1-7dec7f47c8a5" + description: "Water cooled chiller supplying water for chilled and process water systems, with isolation on chilled, process and condensing water side, condensing water heat exchange isolation and cooling thermal power monitoring." + is_canonical: true + implements: + - CH + - SS + - SCHWTC + - CHWDPC + - CWDT + - CWDPM + - CHWSWISOVPM + - CHWRWISOVPM + - PSWISOVPM + - PRWISOVPM + - CWRISOVPM + - HXCRWISOVPM + - CLPM + + +CH_SS_PSWTC_PWDPC_CWDT_CWDPM_PSWISOVPM_CWRISOVPM_CLPM: + guid: "8defc678-ce17-427c-8800-5a0bbe953bd4" + description: "Water cooled process chiller with isolation on condensing and process sides, and cooling thermal power monitoring." + is_canonical: true + implements: + - CH + - SS + - PSWTC + - PWDPC + - CWDT + - CWDPM + - PSWISOVPM + - CWRISOVPM + - CLPM + ################################### ### Existing Non-standard Types ### ################################### diff --git a/ontology/yaml/resources/HVAC/entity_types/CHWS.yaml b/ontology/yaml/resources/HVAC/entity_types/CHWS.yaml index f29a1c22e..731589b27 100644 --- a/ontology/yaml/resources/HVAC/entity_types/CHWS.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/CHWS.yaml @@ -111,6 +111,29 @@ CHWS_SWTC_WDPC_MMCWDPC_BYPVPM_WFRM: - BYPVPM - WFRM +CHWS_SWTC_WDPC_MMCWDPC_WFRM: + guid: "3141b35a-b4ae-4937-8f23-26ca97054a0d" + description: "Chilled water system with supply temperature control, differential pressure and min mechanical cooling differential pressure control and flow monitoring." + is_canonical: true + implements: + - CHWS + - SWTC + - WDPC + - MMCWDPC + - WFRM + +CHWS_SWTC_WDPC2X_MMCWDPC_WSEBYPVPM_WFRM: + guid: "2f840d9d-461f-4a74-a660-c9a88b13bb5a" + description: "Chilled water system with supply temperature control, differential pressure and min mechanical cooling differential pressure control, waterside economizing, and flow monitoring." + is_canonical: true + implements: + - CHWS + - SWTC + - WDPC2X + - MMCWDPC + - WSEBYPVPM + - WFRM + CHWS_SWTC_WDPC2X_BYPVPM_WFRM: guid: "e83ac652-c8c1-4e66-bfa6-5ad734aa9902" description: "Chilled water system with dual differential pressure control, a bypass valve, and flowrate monitoring." @@ -629,6 +652,17 @@ CHWS_SESWTC_SEWDPC_SEWFRM_WSEBYPVM: - SEWFRM - WSEBYPVM +CHWS_SWTC_WDPC2X_WSEBYPVPM_WFRM: + guid: "85ca9a77-bf43-4247-a7e2-b1f25f5fb563" + description: "Chilled water system with dual differential pressure control, waterside economizer bypass, flowrate monitoring." + is_canonical: true + implements: + - CHWS + - SWTC + - WDPC2X + - WSEBYPVPM + - WFRM + ################################### ### Existing Non-standard Types ### ################################### diff --git a/ontology/yaml/resources/HVAC/entity_types/FCU.yaml b/ontology/yaml/resources/HVAC/entity_types/FCU.yaml index ba25c3815..c64550a20 100644 --- a/ontology/yaml/resources/HVAC/entity_types/FCU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/FCU.yaml @@ -1771,6 +1771,93 @@ FCU_DFVSC_RTM_CO2C_HWZTC_CHWZTC_ZHM: - CHWZTC - ZHM +FCU_DSP_DFSS_DFVSMC_HTRC_RMM: + guid: "73330804-8365-4169-b5ae-0965b0c0b0dc" + description: "Fan coil unit with zone temperature and return air temperature control and electric heater." + is_canonical: true + implements: + - FCU + - DSP + - DFSS + - DFVSMC + - HTRC + - RMM + +FCU_DSP_DFSS_DFVSMC_HTZC_MTC_RMM: + guid: "7c88378f-6a35-41d1-84d7-dfc064160120" + description: "Fan coil unit with zone temperature and mixed air temperature control and electric heater." + is_canonical: true + implements: + - FCU + - DSP + - DFSS + - DFVSMC + - HTZC + - MTC + - RMM + +FCU_DSP_DFSS_DFVSMC_HTRC_RMM_DAIDC: + guid: "f7376d4d-d476-4e39-8fc8-732ba9f91d38" + description: "Fan coil unit with zone temperature and return air temperature control and electric heater and isolation damper." + is_canonical: true + implements: + - FCU + - DSP + - DFSS + - DFVSMC + - HTRC + - RMM + - DAIDC + +FCU_DSP_DFSS_DFVSMC_HTRC_RMM_DAIDPC: + guid: "b8e47243-0626-461f-ae68-e690baa3d606" + description: "Fan coil unit with zone temperature and return air temperature control and electric heater and isolation damper." + is_canonical: true + implements: + - FCU + - DSP + - DFSS + - DFVSMC + - HTRC + - RMM + - DAIDPC + +FCU_DFSS_DFVSC_CHWRC_RHC: + guid: "a3c64f5f-487f-4c52-b785-2e4ef329443f" + description: "Fan coil unit withreturn air humidity control and chilled water return air temperature control." + is_canonical: true + implements: + - FCU + - DFSS + - DFVSC + - CHWRC + - RHC + +FCU_CSP_DFSS_DFVSC_CHWRC_RHC: + guid: "453f5dd3-14f4-4d37-aac9-2009345d9761" + description: "Fan coil unit with zone temperature control, return air humidity control and chilled water return air temperature control." + is_canonical: true + implements: + - FCU + - CSP + - DFSS + - DFVSC + - CHWRC + - RHC + +FCU_CSP_DFSS_DFVSC_CHWRC_RHC_DAIDC: + guid: "cf43b4e3-b516-491f-9d4b-eaaa37e7e209" + description: "Fan coil unit with zone temperature control, return air humidity control, chilled water return air temperature control and isolation." + is_canonical: true + implements: + - FCU + - CSP + - DFSS + - DFVSC + - CHWRC + - RHC + - DAIDC + FCU_CSP_DX2ZC_ZHC: guid: "4f6dbf06-0b03-4537-9d53-78855aabea49" description: "Single zone FCU." diff --git a/ontology/yaml/resources/HVAC/entity_types/GENERALTYPES.yaml b/ontology/yaml/resources/HVAC/entity_types/GENERALTYPES.yaml index 3dd4044b8..b7ba3543e 100644 --- a/ontology/yaml/resources/HVAC/entity_types/GENERALTYPES.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/GENERALTYPES.yaml @@ -406,6 +406,7 @@ DOAS: - failed_communication_alarm - smoke_alarm - filter_alarm + - run_mode implements: - EQUIPMENT diff --git a/ontology/yaml/resources/HVAC/entity_types/HX.yaml b/ontology/yaml/resources/HVAC/entity_types/HX.yaml index c1e1ab4d4..7056e3a52 100644 --- a/ontology/yaml/resources/HVAC/entity_types/HX.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/HX.yaml @@ -333,4 +333,25 @@ HX_PSWTC_CHWDT_CHWRWISOVM: - HX - PSWTC - CHWDT - - CHWRWISOVPM \ No newline at end of file + - CHWRWISOVPM + +HX_SCHWTC_CHWFRM_CWDT: + guid: "7249d972-281a-498a-92b6-2d12ff02e6a2" + description: "Condensing/chilled water heat exchanger with chilled water flowrate monitoring." + is_canonical: true + implements: + - HX + - SCHWTC + - CHWFRM + - CWDT + +HX_PSWTC_PWFRM_CWDT_CWSISOVPM: + guid: "94c725f7-e46c-4b41-9c7d-0b44d90f2ef8" + description: "Condensing/process water heat exchanger with process water flowrate monitoring and isolation on condensing return side." + is_canonical: true + implements: + - HX + - PSWTC + - PWFRM + - CWDT + - CWSISOVPM \ No newline at end of file diff --git a/ontology/yaml/resources/HVAC/entity_types/MAU.yaml b/ontology/yaml/resources/HVAC/entity_types/MAU.yaml index 2baa28bc2..f534728b4 100644 --- a/ontology/yaml/resources/HVAC/entity_types/MAU.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/MAU.yaml @@ -903,6 +903,16 @@ MAU_DFSS2X_DFVSC2X_DXDC_HWDC: - DXDC - HWDC +MAU_SFSS_DXSC_SSPC: + guid: "e05424bf-c8c0-40c9-9875-8903dce9bffc" + description: "MAU with supply air static pressure control and supply air temperature control" + is_canonical: true + implements: + - MAU + - SFSS + - DXSC + - SSPC + ############################ ### Remap These Types ### ############################ @@ -1099,4 +1109,4 @@ MAU_SFSS_SFVSC_HTSC_BPC_SHM_NONCANONICAL_2: - MAU_SFSS_SFVSC_HTSC_BPC_SHM - DEPRECATED uses: - - humidification_run_command + - humidification_run_command \ No newline at end of file diff --git a/ontology/yaml/resources/SAFETY/entity_types/ABSTRACT.yaml b/ontology/yaml/resources/SAFETY/entity_types/ABSTRACT.yaml index a3a5d0b41..1fa3497e4 100644 --- a/ontology/yaml/resources/SAFETY/entity_types/ABSTRACT.yaml +++ b/ontology/yaml/resources/SAFETY/entity_types/ABSTRACT.yaml @@ -102,3 +102,13 @@ LM: is_abstract: true uses: - level_status + +REFM: + guid: "591f8a31-dc4b-45a2-8ac1-b0478b7ceaa5" + description: "Refrigerant leak monitoring." + is_abstract: true + opt_uses: + - high_zone_air_refrigerant_concentration_alarm + - failed_zone_air_refrigerant_concentration_alarm + uses: + - zone_air_refrigerant_concentration_sensor \ No newline at end of file diff --git a/ontology/yaml/resources/SAFETY/entity_types/LDS.yaml b/ontology/yaml/resources/SAFETY/entity_types/LDS.yaml index 9ad829313..d5adc03c7 100644 --- a/ontology/yaml/resources/SAFETY/entity_types/LDS.yaml +++ b/ontology/yaml/resources/SAFETY/entity_types/LDS.yaml @@ -108,10 +108,17 @@ LDS_WLA_BCM: LDS_WLCC: guid: "1bc59b7b-cef7-4c39-b7b2-efaae420bf9f" - description: Leak detection sensor with array of leak cable-based sensors." + description: "Leak detection sensor with array of leak cable-based sensors." is_canonical: true uses: - water_leak_detection_alarm - water_leak_alarm - water_leak_cable_distance_sensor - broken_cable_alarm + +LDS_REFM: + guid: "3e43f901-2d8c-4e69-9356-f755780b0f2b" + description: "Refrigerant leak detection." + is_canonical: true + implements: + - REFM \ No newline at end of file diff --git a/ontology/yaml/resources/fields/telemetry_fields.yaml b/ontology/yaml/resources/fields/telemetry_fields.yaml index 240830e35..9cb707c5a 100644 --- a/ontology/yaml/resources/fields/telemetry_fields.yaml +++ b/ontology/yaml/resources/fields/telemetry_fields.yaml @@ -1299,6 +1299,24 @@ literals: - process_water_isolation_valve_command: - OPEN - CLOSED +- process_supply_water_isolation_valve_percentage_command: + fixed_min: 0.0 + fixed_max: 100.0 +- process_supply_water_isolation_valve_percentage_sensor: + fixed_min: 0.0 + fixed_max: 100.0 +- failed_process_supply_water_isolation_valve_alarm: + - ACTIVE + - INACTIVE +- process_return_water_isolation_valve_percentage_command: + fixed_min: 0.0 + fixed_max: 100.0 +- process_return_water_isolation_valve_percentage_sensor: + fixed_min: 0.0 + fixed_max: 100.0 +- failed_process_return_water_isolation_valve_alarm: + - ACTIVE + - INACTIVE - process_water_valve_percentage_command: fixed_min: 0.0 fixed_max: 100.0 @@ -1621,6 +1639,15 @@ literals: - heat_exchange_return_water_isolation_valve_percentage_command: fixed_min: 0.0 fixed_max: 100.0 +- heat_exchange_condensing_return_water_isolation_valve_percentage_command: + fixed_min: 0.0 + fixed_max: 100.0 +- heat_exchange_condensing_return_water_isolation_valve_percentage_sensor: + fixed_min: 0.0 + fixed_max: 100.0 +- failed_heat_exchange_condensing_return_water_isolation_valve_alarm: + - ACTIVE + - INACTIVE - heat_exchange_supply_water_isolation_valve_status: - OPEN - CLOSED